Dayton Installation, Operation, Maintenance and Parts Manual
Models 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88
A tube heater system is being installed in 70’ (L) x 40’ (W) space with 12’ ceilings. Two overhead doors are located at one
end and an equipment storage area exists on one side. The calculated heat load is 300,000 BTU/H.
Design Scenario
Figure 2.1 Poor Design
Two burners (150,000 BTU/H each)
are placed at one end, opposite the
area of highest demand (overhead
doors).
Recommended mounting heights
are not observed.
Produces an uneven heat
distribution.
Figure 2.2 Good Design
Four burners (75,000 BTU/H each)
are placed in each corner. Burner
(hotter) ends direct heat to areas of
highest head demand.
Recommended mounting heights
observed.
Distributes heat more evenly.
9
Doors and
tracks
Doors and
tracks
Equipment storage
Better Heat Distribution
Sidewall Vent (2 total)
40’
70
Gas Supply
20’ - 75,000 BTU
(4 total)
Good Design
Doors and
tracks
Too Cold
Too Hot
Equipment storage
40’
60’ - 150,000 BTU
(2 total)
Doors and
tracks
70
Gas Supply
Poor Design